Fire-rated storage container RFP 315.20 Li-Ion
Item number: 274108W
- Area of application: best option when larger quantities or larger-sized lithium energy storage devices (batteries) need to be accommodated.
- Fire-rated store: tested and approved as a complete system with 90 minute fire protection (REI 90) from inside and outside. International designs meeting country-specific legislation (e.g. REI 120). Install directly next to the external wall of neighbouring buildings or as a fire-rated separate area, e.g. in a production hall.
- Storage levels: fitted with removable, hot-dip galvanised grids.
- Base: tested, single-piece spill pallet with easily removable hot-dip galvanised grids. An accessible concrete pad can be provided separately if access underneath for a hand operated electric stacker is required.
- External cladding: galvanised components with 2 layers of paint give long lasting protection. Fire protection panels (A class material, non-combustible) with high insulation properties.
- Door variants: with 2-wing EI₂ 90-C door on the long side of the room system. A door sequence controller ensures the doors close reliably. Door opening angle: 90° (minimum), 102° (door does not protrude beyond the side of the body), 115° (standard, from this point the effective clear dimension is now fully accessible), 128° (maximum).
- Structural analysis: to Eurocode 3 (EN 1993) measured for a characteristic wind load with a dynamic pressure of qw = 0.585 kN/m² and a characteristic ground snow load of sk = 2.5 kN/m²; adequately dimensioned according to DIN 4149, EN 1998-1:2004 for earthquake zone 3. Available with additional equipment for up to wind load zone 4, terrain category I (qw= 1.064 kN/m²) and for up to ground snow load sk = 5.86 kN/m².
Structural analysis
The structural calculations for the technical room system are based on Eurocode 3 (EN 1993). The loads on the structure are measured according to Eurocode 1 (EN 1991-1-3) for a characteristic wind load qk,w = 0.585 kN/m² and a ground snow load sk = 2.5 kN/m². The structure is also designed for earthquake zone 3 according to EN 4149, EN 1998-1:2004. With additional equipment up to wind load zone 4 with terrain category I (qk,w = 1.064 kN/m²) or up to ground snow load sk = 5.86 kN/m².
Roof drainage
Roof drainage channels rain water to the frame running around the edge and drains it away on the short sides either to the left or the right.
Full descriptionMon - Thu: 08:30 - 17:00 Fri: 08:30 - 16:00
Product description
- Area of application: best option when larger quantities or larger-sized lithium energy storage devices (batteries) need to be accommodated.
- Fire-rated store: tested and approved as a complete system with 90 minute fire protection (REI 90) from inside and outside. International designs meeting country-specific legislation (e.g. REI 120). Install directly next to the external wall of neighbouring buildings or as a fire-rated separate area, e.g. in a production hall.
- Storage levels: fitted with removable, hot-dip galvanised grids.
- Base: tested, single-piece spill pallet with easily removable hot-dip galvanised grids. An accessible concrete pad can be provided separately if access underneath for a hand operated electric stacker is required.
- External cladding: galvanised components with 2 layers of paint give long lasting protection. Fire protection panels (A class material, non-combustible) with high insulation properties.
- Door variants: with 2-wing EI₂ 90-C door on the long side of the room system. A door sequence controller ensures the doors close reliably. Door opening angle: 90° (minimum), 102° (door does not protrude beyond the side of the body), 115° (standard, from this point the effective clear dimension is now fully accessible), 128° (maximum).
- Structural analysis: to Eurocode 3 (EN 1993) measured for a characteristic wind load with a dynamic pressure of qw = 0.585 kN/m² and a characteristic ground snow load of sk = 2.5 kN/m²; adequately dimensioned according to DIN 4149, EN 1998-1:2004 for earthquake zone 3. Available with additional equipment for up to wind load zone 4, terrain category I (qw= 1.064 kN/m²) and for up to ground snow load sk = 5.86 kN/m².
Structural analysis
The structural calculations for the technical room system are based on Eurocode 3 (EN 1993). The loads on the structure are measured according to Eurocode 1 (EN 1991-1-3) for a characteristic wind load qk,w = 0.585 kN/m² and a ground snow load sk = 2.5 kN/m². The structure is also designed for earthquake zone 3 according to EN 4149, EN 1998-1:2004. With additional equipment up to wind load zone 4 with terrain category I (qk,w = 1.064 kN/m²) or up to ground snow load sk = 5.86 kN/m².
Roof drainage
Roof drainage channels rain water to the frame running around the edge and drains it away on the short sides either to the left or the right.
Technical data
Model | RFP 315.20 Li-Ion |
Clear bay depth [mm] | 1440 |
Dimensions (without attachments) W x D x H [mm] | 3660 x 1784 x 2630 |
Bay dimensions W x D x H [mm] | 2917 x 1440 x 1954 |
Door position | Long side |
Door version | hinged door |
Door design | 2 wing doors |
Door hinge | both sides |
Fire resistance | 90 minutes |
Load capacity [kg/m²] | 1250 |
Containment volume [l] | 1400 |
Number of storage levels | 1 |
Weight [kg] | 2500 |